APPLICATION
To supply power from the utility’s lines to the consumer’s weatherhead. For service at 600 volts or less (phase to phase) at a conductor temperature of 75°C maximum for polyethylene insulation or 90°C maximum for crosslinked polyethylene (XLP) insulated conductors.
PRODUCT FEATURES
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC or ACSR.
STANDARDS:
Service drop cable meets or exceeds the following ASTM specifications:
• B-230 Aluminum Wire, 1350-H19 for Electrical Purposes
• B-231 Aluminum Conductors, Concentric-Lay-Stranded
• B-232 Aluminum Conductors, Concentric-Lay-Stranded,
Coated Steel Reinforced (ACSR)
• B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors
• B-901 Compressed Round Stranded Aluminum Conductors
Using Single Input Wire
• ANSI/ICEA S-76-474

SPECIFICATIONS
KINGWIRE TRIPLEX SERVICE DROP – AAAC-ALLOY NEUTRAL MESSENGER |
||||||||||
| Code Word | Phase Conductors | Bare Neutral | Weight per 1000 ft. (lbs) |
Rating (AMPS) | ||||||
| Size AWG |
Strand | Insulation Thickness (MLS) |
Size AWG |
Strand | Breaking Strength (lbs) | XLP | Poly | XLP | Poly | |
| Minex | 6 | Solid | 45 | 6 | 7 | 1,110 | 106.6 | 102.9 | 85 | 70 |
| Hippa | 6 | 7/w | 45 | 6 | 7 | 1,110 | 107.0 | 105.7 | 85 | 70 |
| Prawn | 4 | Solid | 45 | 4 | 7 | 1,760 | 158.4 | 154.1 | 110 | 90 |
| Barnacles | 4 | 7/w | 45 | 4 | 7 | 1,760 | 160.0 | 157.0 | 110 | 90 |
| Shrimp | 2 | 7/w | 45 | 2 | 7 | 2,800 | 243.0 | 238.0 | 150 | 115 |
| Gammarus | 1/0 | 7/w | 60 | 1/0 | 7 | 4,460 | 390.0 | 384.0 | 200 | 155 |
| Leda | 1/0 | 19/w | 60 | 1/0 | 7 | 4,460 | 384.0 | 378.0 | 200 | 155 |
| Dungenese | 2/0 | 7/w | 60 | 2/0 | 7 | 5,390 | 481.0 | 474.0 | 230 | 180 |
| Cyclops | 2/0 | 19/w | 60 | 2/0 | 7 | 5,390 | 473.0 | 467.0 | 230 | 180 |
| Flustra | 3/0 | 19/w | 60 | 3/0 | 7 | 6,790 | 596.0 | 589.1 | 260 | 205 |
| Lepas | 4/0 | 19/w | 60 | 4/0 | 7 | 8,560 | 725.0 | 716.0 | 300 | 235 |
KINGWIRE TRIPLEX SERVICE DROP – ALUMINUM CONDUCTOR – AAAC – ALLOY REDUCED NEUTRAL MESSENGER |
||||||||||
| Code Word | Phase Conductors | Bare Neutral | Weight per 1000 ft. (lbs) |
Rating (AMPS) | ||||||
| Size AWG |
Strand | Insulation Thickness (MLS) |
Size AWG |
Strand | Breaking Strength (lbs) | XLP | Poly | XLP | Poly | |
| Artemia | 4 | Solid | 45 | 6 | 7 | 1,110 | 134.0 | 132.0 | 110 | 90 |
| Crab | 4 | 7/w | 45 | 6 | 7 | 1,110 | 144.0 | 141.2 | 110 | 90 |
| Solaster | 2 | 7/w | 45 | 4 | 7 | 1,760 | 216.0 | 212.6 | 150 | 115 |
| Sandcrab | 1/0 | 7/w | 60 | 2 | 7 | 2,800 | 348.0 | 341.0 | 200 | 155 |
| Echinus | 1/0 | 19/w | 60 | 2 | 7 | 2,800 | 342.0 | 336.0 | 200 | 155 |
| Crayfish | 2/0 | 7/w | 60 | 1 | 7 | 3,530 | 452.6 | 422.5 | 230 | 180 |
| Sipho | 2/0 | 19/w | 60 | 1 | 7 | 3,530 | 441.0 | 422.5 | 230 | 180 |
| Fulgar | 3/0 | 19/w | 60 | 1/0 | 7 | 4,460 | 525.0 | 518.0 | 260 | 205 |
| Arca | 4/0 | 19/w | 60 | 2/0 | 7 | 5,360 | 640.0 | 632.0 | 300 | 235 |
KINGWIRE TRIPLEX SERVICE DROP – ALUMINUM CONDUCTOR – AAC – NEUTRAL MESSENGER |
||||||||||
| Code Word | Phase Conductors | Bare Neutral | Weight per 1000 ft. (lbs) |
Rating (AMPS) | ||||||
| Size AWG |
Strand | Insulation Thickness (MLS) |
Size AWG |
Strand | Breaking Strength (lbs) | XLP | Poly | XLP | Poly | |
| Haiotis | 6 | Solid | 45 | 6 | 7 | 563 | 102.5 | 98.8 | 85 | 70 |
| Patella | 6 | 7/w | 45 | 6 | 7 | 563 | 104.0 | 101.6 | 85 | 70 |
| Fusus | 4 | Solid | 45 | 4 | 7 | 881 | 151.9 | 147.6 | 110 | 90 |
| Oyster | 4 | 7/w | 45 | 4 | 7 | 881 | 154.0 | 151.7 | 110 | 90 |
| Clam | 2 | 7/w | 45 | 2 | 7 | 1,350 | 232.0 | 228.0 | 150 | 115 |
| Murex | 1/0 | 7/w | 1/0 | 1/0 | 7 | 1,990 | 374.0 | 367.0 | 200 | 155 |
| Purpura | 1/0 | 19/w | 1/0 | 1/0 | 7 | 1,990 | 368.0 | 362.0 | 200 | 155 |
| Nassa | 2/0 | 7/w | 2/0 | 2/0 | 7 | 2,510 | 461.0 | 453.0 | 230 | 180 |
| Melita | 3/0 | 19/w | 3/0 | 3/0 | 19 | 3,310 | 585.2 | 562.9 | 260 | 205 |
| Portunus | 4/0 | 19/w | 4/0 | 4/0 | 19 | 4,020 | 693.0 | 684.0 | 300 | 235 |
| Nannynose | 336.4 | 19/w | 336.4 | 336.4 | 19 | 6,146 | 1,111.0 | 1,096.0 | 380 | 290 |
KINGWIRE TRIPLEX SERVICE DROP – ALUMINUM CONDUCTOR – FULL SIZE ACSR MESSENGER |
||||||||||
| Code Word | Phase Conductors | Bare Neutral | Weight per 1000 ft. (lbs) |
Rating (AMPS) | ||||||
| Size AWG |
Strand | Insulation Thickness (MLS) |
Size AWG |
Strand | Breaking Strength (lbs) | XLP | Poly | XLP | Poly | |
| Paludina | 6 | Solid | 45 | 6 | 6/1 | 1,190 | 114 | 113 | 85 | 70 |
| Voluta | 6 | 7/w | 45 | 6 | 6/1 | 1,190 | 115 | 112 | 85 | 70 |
| Whelk | 4 | Solid | 45 | 4 | 6/1 | 1,860 | 163 | 161 | 110 | 90 |
| Periwinkle | 4 | 7/w | 45 | 4 | 6/1 | 1,860 | 172 | 169 | 110 | 90 |
| Conch | 2 | 7/w | 45 | 2 | 6/1 | 2,850 | 262 | 257 | 150 | 115 |
| Neritina | 1/0 | 7/w | 60 | 1/0 | 6/1 | 4,380 | 420 | 414 | 200 | 115 |
| Cenia | 1/0 | 19/w | 60 | 1/0 | 6/1 | 4,380 | 414 | 408 | 200 | 115 |
| Runcina | 2/0 | 7/w | 60 | 2/0 | 6/1 | 5,310 | 519 | 512 | 230 | 180 |
| Triton | 2/0 | 19/w | 60 | 2/0 | 6/1 | 5,310 | 511 | 505 | 230 | 180 |
| Cherrystone | 3/0 | 7/w | 60 | 3/0 | 6/1 | 6,620 | 656 | 643 | 260 | 205 |
| Mursia | 3/0 | 19/w | 60 | 3/0 | 6/1 | 6,620 | 633 | 626 | 260 | 205 |
| Razor | 4/0 | 7/w | 60 | 4/0 | 6/1 | 8,350 | 814 | 799 | 300 | 235 |
| Zuzara | 4/0 | 19/w | 60 | 4/0 | 6/1 | 8,350 | 785 | 777 | 300 | 235 |
| Limpet | 336.4 | 19/w | 80 | 336.4 | 18/1 | 8,680 | 1,160 | 1,147 | 300 | 290 |
KINGWIRE TRIPLEX SERVICE DROP – ALUMINUM CONDUCTOR – ACSR REDUCED SIZE MESSENGER |
||||||||||
| Code Word | Phase Conductors | Bare Neutral | Weight per 1000 ft. (lbs) |
Rating (AMPS) | ||||||
| Size AWG |
Strand | Insulation Thickness (MLS) |
Size AWG |
Strand | Breaking Strength (lbs) | XLP | Poly | XLP | Poly | |
| Scallop | 4 | Solid | 45 | 6 | 6/1 | 1,190 | 142 | 139 | 110 | 90 |
| Strombus | 4 | 7/w | 45 | 6 | 6/1 | 1,190 | 151 | 148 | 110 | 90 |
| Cockle | 2 | 7/w | 45 | 4 | 6/1 | 1,860 | 228 | 224 | 150 | 115 |
| Janthina | 1/0 | 7/w | 60 | 2 | 6/1 | 2,850 | 367 | 360 | 200 | 155 |
| Ranella | 1/0 | 19/w | 60 | 2 | 6/1 | 2,850 | 361 | 356 | 200 | 155 |
| Cavolinia | 2/0 | 7/w | 60 | 1 | 6/1 | 3,550 | 452 | 444 | 230 | 180 |
| Clio | 2/0 | 19/w | 60 | 1 | 6/1 | 3,550 | 444 | 437 | 230 | 180 |
| Sanddollar | 3/0 | 7/w | 60 | 1/0 | 6/1 | 4,380 | 570 | 557 | 260 | 205 |
| Aega | 3/0 | 19/w | 60 | 1/0 | 6/1 | 4,380 | 565 | 552 | 260 | 205 |
| Cutlefish | 4/0 | 7/w | 60 | 2/0 | 6/1 | 5,310 | 706 | 691 | 300 | 235 |
| Cerapus | 4/0 | 19/w | 60 | 2/0 | 6/1 | 5,310 | 678 | 670 | 300 | 235 |
| Cowry | 336.4 | 19/w | 80 | 4/0 | 6/1 | 8,350 | 1,135 | 1,093 | 380 | 290 |
* Note: Designated sizes are ACSR 6/1 diameter equivalent resistivity per ASTM-B-399 for 6201. Conductor temperature of 90°C for XLP, 75°C for Poly; ambient temperatures of 40°C; emissivity 0.9; 2ft/sec. wind in sun.
** To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.
The data is approximate and subject to normal manufacturing tolerances.
SPECIFICATIONS